The Office of Investigations and Analysis released Marine Safety Alert 07-18, “Ethylene vapors activate carbon monoxide alarm: Take action, retreat, and avoid harm,” regarding reports that Port State Control Officers (PSCOs) received alarms on their portable 4 gas meters giving a reading of 60 to 100 parts per-million (PPM) carbon monoxide (CO), during recent examinations of a liquefied gas carrier that had cargo tanks containing ethylene vapors.
A certified marine chemist traced the source of the vapors to an eight-inch crack on a cargo vapor line. PSCOs initially thought the alarm was related to a combustion event and did not suspect the ethylene vapors were the source because they did not get a Lower Explosive Limit (LEL) reading on their monitors. The chemist indicated that the LEL most likely never alarmed because of high winds on deck. He further explained that the molecular weight of ethylene (28 g/mol) was identical to the molecular weight of CO, which accounted for the CO PPM readings. Coast Guard personnel contacted the manufacturer who confirmed that gases such as methane, propane, ethylene and mercaptan, could actuate the CO sensor without ever coming into the range of the LEL limits.
As a result of these events the Coast Guard strongly reminds all surveyors, marine inspectors, port state control examiners, and any other persons utilizing portable gas monitors and detectors while working onboard liquefied gas carriers to remain acutely aware that the ethylene gas vapors can exhibit cross-sensitivity. This issue is not limited to the monitors that the Coast Guard uses but also those made by other manufacturers. Everyone using a monitor must be aware that if the CO alarm goes off it may be an indication of dangerous gases or chemical vapors and not the presence of CO. When the alarm sounds, users must take corrective action to minimize exposure risks.
This safety alert is provided for informational purposes only and does not relieve any domestic or international safety, operational or material requirement. Developed by Sector Houston-Galveston and the Liquefied Gas Carrier National Center of Expertise (LGC NCOE), Port Arthur, Texas and distributed by the Office of Investigations and Analysis. Questions may be sent to HQS-PF-fldr-CG-INV@uscg.mil or lgcncoe@uscg.mil.